  1.                          SECTION 09841
  2.  
  3.                      ACOUSTICAL WALL PANELS
  4. NOTE ** Unique Concepts, Inc. FABRI-TRAK(R) acoustical wall
  5.         panel system.
  6. NOTE **
  7. NOTE ** This section is based on products manufactured by
  8.         Unique Concepts, Inc., located at the following
  9.         address:
  10. NOTE **    1804 NW Madrid Way
  11. NOTE **    Boca Raton, FL  33432
  12. NOTE **    Tel:  (561) 395-7677
  13. NOTE **    Fax:  (561) 395-8990
  14. NOTE **
  15. NOTE ** SECTION 09841 - ACOUSTICAL WALL PANELS, Copyright
  16.         1997, The Architect's Catalog, Inc.
  17.  
  18.  
  19. PART 1  GENERAL
  20.  
  21. 1.1 SECTION INCLUDES
  22. NOTE ** Delete items below not required for project.
  23.  
  24.     A.  Acoustical Fabric Panel System.
  25.  
  26.     B.  Noise-Reducing Fabric Panel System.
  27.  
  28. 1.2 RELATED SECTIONS
  29. NOTE ** Delete any sections below not relevant to this
  30.         project; add others as required.
  31.  
  32.     A.  Section 01110 - Summary of Work.
  33.  
  34.     B.  Section 06400 - Architectural Woodwork.
  35.  
  36.     C.  Section 08110 - Metal Doors and Frames.
  37.  
  38.     D.  Section 08210 - Wood Doors.
  39.  
  40.     E.  Section 09200 - Plaster and Gypsum Board.
  41.  
  42.     F.  Section 09500 - Ceilings.
  43.  
  44.     G.  Section 09700 - Wall Finishes.
  45.  
  46.     H.  Section 09900 - Paints and Coatings.
  47.  
  48.     I.  Section 12050 - Fabrics.
  49.  
  50.     J.  Affected sections of Divisions 15 and 16.
  51.  
  52. 1.3 REFERENCES
  53. NOTE ** Delete references from the list below that are not
  54.         actually required by the text of the edited
  55.         section.
  56.  
  57.     A.  ASTM E 84 - Standard Test Method for Surface Burning
  58.         Characteristics of Building Materials.
  59.  
  60.     B.  ASTM E 90 - Standard Test Method for Laboratory
  61.         Measurement of Airborne-Sound Transmission Loss of
  62.         Building Partitions.
  63.  
  64. 1.4 SYSTEM DESCRIPTION
  65. NOTE ** Retain one or both of the following two paragraphs,
  66.         as applicable to systems specified for project.
  67.  
  68.     A.  Acoustical Fabric Panel System:
  69.         1.  Thermal resistance:  R-value 1.4 (0.24 metric
  70.             equivalent).
  71.         2.  Noise reduction coefficient (NRC), when tested in
  72.             accordance with ASTM E 90 at 1000-4000 Hertz level:
  73.             a.  Over concrete substrate:  0.90.
  74.             b.  Over drywall substrate:  0.67.
  75.         3.  Flammability, when tested in accordance with ASTM E
  76.             84:  Flame spread index 25 or less; smoke developed
  77.             index 450 or less.
  78.  
  79.     B.  Noise-Reducing Fabric Panel System:
  80.         1.  Thermal resistance:  R-value 4.3 (0.75 metric
  81.             equivalent).
  82.         2.  Noise reduction coefficient (NRC), when tested in
  83.             accordance with ASTM E 90 at 1000-4000 Hertz level:
  84.             0.97.
  85.         3.  Flammability, when tested in accordance with ASTM E
  86.             84:  Flame spread index of 12.1; smoke developed
  87.             index of 24.3.
  88.  
  89. 1.5 SUBMITTALS
  90.  
  91.     A.  Submit under provisions of Section 01300.
  92.  
  93.     B.  Product Data:  Manufacturer's descriptive literature for
  94.         fabric panel systems components.
  95. NOTE ** Due to the variety of design concepts that can be
  96.         executed, the careful checking of shop drawing
  97.         information, based on the drawing details of the
  98.         Contract Documents, will be required to ensure that
  99.         finished installation reflects design concepts.
  100.  
  101.     C.  Shop Drawings:
  102.         1.  Submit scaled and dimensioned elevation drawings of
  103.             each surface in project to receive fabric wall
  104.             panels, indicating fabric wall panel layouts; minimum
  105.             scale 1/2 inch equals 1 foot (1:20).
  106.         2.  Indicate for each panel in project:
  107.             a.  Location.
  108.             b.  Size.
  109.             c.  Type, including frame, core, and fabric finish
  110.                 components.
  111.         3.  Submit drawings indicating construction details of
  112.             fabric wall panels; include details of interface with
  113.             adjacent construction.
  114.  
  115.     D.  Verification Samples:
  116. NOTE ** Delete the following sub-paragraph if specifying
  117.         Owner-supplied fabrics in reveals, or no reveals in
  118.         wall panels layouts.
  119.         1.  Two samples of each specified reveal material,
  120.             minimum size 12 inches (304 mm) long.
  121. NOTE ** Delete the following sub-paragraph if specifying
  122.         Owner-supplied fabrics.
  123.         2.  Two samples of each specified fabric, minimum size 12
  124.             inches (304 mm) square.
  125.  
  126.     E.  Quality Assurance Submittals:
  127.         1.  Certified reports from independent testing laboratory
  128.             supporting compliance of fabric wall panels to
  129.             specified noise-reducing, thermal resistance, and
  130.             surface burning requirements.
  131.         2.  Manufacturer's certification that:
  132.             a.  Fabric wall panel systems meet specified
  133.                 regulatory requirements.
  134.             b.  Installer of manufacturer's product is approved.
  135.         3.  Installer's certification that fabrics selected for
  136.             fabric wall panel systems have correct properties for
  137.             use in systems.
  138.         4.  Manufacturer's instructions:
  139.             a.  Printed installation instructions for system
  140.                 components, including product storage
  141.                 requirements.
  142.  
  143. 1.6 QUALITY ASSURANCE
  144.  
  145.     A.  Installer Qualifications:  Approved by fabric wall panel
  146.         system manufacturer.
  147.  
  148.     B.  Regulatory Requirements:  Fabric wall panel systems
  149.         certified Class 1 or Class A by regulating building code.
  150. NOTE ** Delete the following paragraph if not required.
  151.  
  152.     C.  Mock-Ups:
  153.         1.  Construct mock-ups using materials specified in this
  154.             section.
  155. NOTE ** Retain one of the following two sub-paragraphs.
  156.         2.  Construct mock-ups as directed, at location indicated
  157.             or directed.
  158.         3.  Construct mock-ups at location indicated or directed,
  159.             and as follows:
  160.             a.  Size:  __ feet (__ mm) by __ feet (__ mm).
  161.             b.  Include the following:  _____________________.
  162.         4.  Obtain Architect's acceptance of mock-ups before
  163.             beginning construction activities of this section;
  164.             accepted mock-ups will be standard by which completed
  165.             construction activities of this section is judged.
  166. NOTE ** Retain one of the following two sub-paragraphs.
  167.         5.  Mock-ups may not remain as part of Work.
  168.         6.  Accepted mock-ups may remain as part of Work.
  169. NOTE ** Delete the following paragraph if not required.
  170.  
  171.     D.  Pre-Installation Meeting:
  172.         1.  Convene at job site seven (7) calendar days prior to
  173.             scheduled beginning of construction activities of
  174.             this section to review requirements of this section.
  175.         2.  Require attendance by representatives of the
  176.             following:
  177.             a.  Installer of this section.
  178.             b.  Other entities directly affecting, or affected
  179.                 by, construction activities of this section.
  180.         3.  Notify Architect four (4) calendar days in advance of
  181.             scheduled meeting date.
  182.  
  183. 1.7 DELIVERY, STORAGE, AND HANDLING
  184.  
  185.     A.  Store products of this section in manufacturer's unopened
  186.         packaging until installation.
  187.  
  188.     B.  Maintain storage area conditions for products of this
  189.         section in accordance with manufacturer's instructions
  190.         until installation.
  191.  
  192. 1.8 SEQUENCING
  193.  
  194.     A.  Sequence construction activities of this section to begin
  195.         in an area only after all other construction activities
  196.         are completed and all other finishes are installed.
  197.  
  198.     B.  Do not allow construction activities of this section to
  199.         begin in an area before obtaining installer's acceptance
  200.         of conditions in accordance with EXAMINATION Article of
  201.         PART 3 of this section.
  202. NOTE ** Delete the following Article if not required for
  203.         project, or if specifying Owner-supplied fabrics;
  204.         revise quantities as applicable to scope of
  205.         installation of fabric wall panels.
  206.  
  207. 1.9 MAINTENANCE
  208.  
  209.     A.  Extra Materials:  For each fabric specified, supply to
  210.         Owner a single length of fabric from the same bolt as
  211.         that installed, equal to 10 percent of the quantity
  212.         installed or 5 linear yards (5 m), whichever is greater.
  213.  
  214.  
  215. PART 2  PRODUCTS
  216.  
  217. 2.1 MANUFACTURERS
  218.  
  219.     A.  Acceptable Manufacturer:  Unique Concepts, Inc.; 1804 NW
  220.         Madrid Way, Boca Raton, FL  33432. ASD. Tel: (561) 395-
  221.         7677. Fax: (561) 395-8990.
  222. NOTE ** Delete one of the two following paragraphs;
  223.         coordinate with Division 1 requirements.
  224.  
  225.     B.  Requests for substitution will be considered in
  226.         accordance with provisions of Section 01600.
  227.  
  228.     C.  Substitutions:  Not permitted.
  229.  
  230.     D.  Unless otherwise specified for an individual product or
  231.         material, supply all products specified in this section
  232.         from the same manufacturer.
  233.  
  234. 2.2 ACOUSTICAL FABRIC PANEL SYSTEM
  235. NOTE ** The following two paragraphs are for the 3/8 inch
  236.         FABRI-TRAK(R) Upholstered Wall System.
  237.  
  238.     A.  Concealed Framework:
  239.         1.  Acceptable system:  FABRI-TRAK(R) Upholstered Wall
  240.             System.
  241.         2.  Description:  Rigid vinyl extrusions, formed as
  242.             single piece, with integral clamping jaws, 1/2 inch
  243.             (12 mm) nailing flange, 1 inch (25 mm) wide edge.
  244.         3.  Projection From Wall:  3/8 inch (9 mm).
  245.         4.  Profile:  One or more of the following:
  246.             a.  Radius edge.
  247.             b.  Square edge.
  248.             c.  Beveled edge.
  249.             d.  Monolithic edge.
  250.  
  251.     B.  Core Material:  One or more of the following:
  252.         1.  Acoustical core material:  Fire-retardant
  253.             compressible polyester padding, 1/2 inch (12 mm)
  254.             thick.
  255.         2.  Tackable core material:  Fire-retardant rigid
  256.             material, 3/8 inch (9 mm) thick.
  257.         3.  Nailable core material:  Fire-retardant treated
  258.             veneer plywood, 3/8 inch (9 mm) thick.
  259.  
  260. 2.3 NOISE-REDUCING FABRIC PANEL SYSTEM
  261. NOTE ** The following paragraphs are for the 1 inch or 2
  262.         inch FABRI-TRAK(R) Upholstered Wall System.
  263.  
  264.     A.  Concealed Framework:
  265.         1.  Acceptable system:  FABRI-TRAK(R) Upholstered Wall
  266.             System.
  267.         2.  Description:  Rigid vinyl extrusions, formed as
  268.             single piece, with integral clamping jaws, 1 inch (25
  269.             mm) nailing flange, 3/4 inch (19 mm) wide edge.
  270. NOTE ** Delete one of the following two paragraphs.
  271.         3.  Projection From Wall:  1 inch (25 mm).
  272.         4.  Projection From Wall:  2 inches (50 mm).
  273.         5.  Profile:  One or more of the following:
  274.             a.  Radius edge.
  275.             b.  Square (monolithic) edge.
  276.             c.  Beveled edge.
  277.  
  278.     B.  Core Material:  One or more of the following:
  279.         1.  Noise-reducing core material:  Fire-retardant glass-
  280.             fiber padding, 1-1/8 inch (28 mm) thick, 6 pounds per
  281.             cubic foot (96 kg/cu m) density.
  282.         2.  Tackable core material:  Two layers fire-retardant
  283.             rigid material, 1/2 inch (12 mm) thick.
  284.         3.  Nailable core material:  Two layers fire-retardant
  285.             treated veneer plywood, 1/2 inch (12 mm) thick.
  286.  
  287. 2.4 FABRICS
  288. NOTE ** Retain the following paragraph if specifying
  289.         fabrics in this section, to be obtained by the
  290.         installer.  If only one type fabric is required,
  291.         delete Type designation; if more than one type is
  292.         required, duplicate paragraph for each type, assign
  293.         a Type designation for each fabric, and edit for
  294.         project requirements.  Obtain installer's
  295.         assistance to assess suitability of selected
  296.         fabrics.
  297.  
  298.     A.  Fabric Type __:
  299.         1.  Manufacturer:  ____________.
  300.         2.  Width:  ____________.
  301.         3.  Material:  ____________, flame retardant treated.
  302.         4.  Style:  ____________.
  303. NOTE ** Retain the following paragraph if fabrics are
  304.         specified in the following section; edit section
  305.         number if another section is used.  Coordinate with
  306.         RELATED SECTIONS Article in PART 1 of this section.
  307.  
  308.     B.  Fabrics:  Specified in Section 12050.
  309. NOTE ** Retain the following paragraph if fabrics are to be
  310.         supplied by Owner; edit section number if another
  311.         section is used.  Coordinate with RELATED SECTIONS
  312.         Article in PART 1 of this section, and with the
  313.         affected section.
  314. NOTE ** Include requirement in the affected section that
  315.         Owner's responsibility will include furnishing
  316.         fabric information and samples to the installer, so
  317.         that the installer can assess the suitability of
  318.         the fabric(s) to be supplied for panels.
  319.  
  320.     C.  Fabrics:  Supplied by Owner; specified in Section 01110.
  321.  
  322. 2.5 ACCESSORIES
  323. NOTE ** Retain the following paragraph if specifying reveal
  324.         other than fabric for fabric panels.  If only one
  325.         type reveal is required, delete Type designation;
  326.         if more than one type is required, duplicate
  327.         paragraph for each type, assign a Type designation
  328.         for each reveal, and edit for project requirements.
  329.  
  330.     A.  Reveal Type __:
  331.         1.  Manufacturer's standard laminated wood reveal strip,
  332.             1/2 inch (12 mm) thick, with beveled long edges.
  333.         2.  Width:  __ inch(es) (__ mm).
  334.         3.  Finish:  __________________.
  335.         4.  Fasteners for Concealed Framing:  Types and sizes
  336.             specified in manufacturer's instructions for
  337.             substrate types.
  338.  
  339. PART 3  EXECUTION
  340.  
  341. 3.1 EXAMINATION
  342.  
  343.     A.  Installer's Examination:
  344.         1.  Have installer of this section examine conditions
  345.             under which construction activities of this section
  346.             are to be performed, then submit written notification
  347.             if such conditions are unacceptable.
  348.         2.  Transmit two copies of installer's report to
  349.             Architect within 24 hours of receipt.
  350.         3.  Beginning construction activities of this section
  351.             before unacceptable conditions have been corrected is
  352.             prohibited.
  353.         4.  Beginning construction activities of this section
  354.             indicates installer's acceptance of conditions.
  355.  
  356. 3.2 INSTALLATION
  357.  
  358.     A.  Install systems in accordance with shop drawings and
  359.         manufacturer's instructions.
  360.  
  361.     B.  Install concealed framework extrusions in maximum lengths
  362.         practical:
  363.         1.  Form end-to-end butt joints with hairline joints.
  364.         2.  Where horizontal and vertical concealed framework
  365.             extrusions intersect, form hairline mitered joints.
  366.         3.  Joint locations shall not be visible in finished
  367.             Work.
  368.  
  369.     C.  Install core materials so that joints between core
  370.         materials and edges of concealed framework extrusions are
  371.         not visible in finished Work; rabbet edges of rigid core
  372.         materials for flush fit at nailing flanges of concealed
  373.         framework extrusions.
  374.  
  375.     D.  Install fabrics without visible wrinkles or folds,
  376.         maintaining horizontal/vertical alignment of warp/woof of
  377.         fabric; force fabric edges into clamping jaws, using
  378.         tools and techniques that will not damage finish of
  379.         fabrics.
  380. NOTE ** Delete the following paragraph if no panel reveals
  381.         in project.
  382.  
  383.     E.  Install reveal materials in maximum lengths practical.
  384.  
  385. 3.3 PROTECTION OF INSTALLED PRODUCTS
  386.  
  387.     A.  Protect finished installation from damage by subsequent
  388.         construction activities until Substantial Completion.
  389.  
  390.     B.  If areas of fabrics become soiled by subsequent
  391.         construction activities, clean in accordance with fabric
  392.         manufacturer's recommendations; replace soiled areas that
  393.         cannot be cleaned to Architect's acceptance in accordance
  394.         with the following paragraph.
  395.  
  396.     C.  Where fabric has become soiled, or otherwise visibly
  397.         damaged, to the extent that repairs cannot be made to the
  398.         Architect's acceptance, have installer of this section
  399.         remove entire run of fabric and replace with new material
  400.         in accordance with requirements of this section; cost of
  401.         replacement shall not affect Contract Sum.
  402. NOTE ** The following sample schedule may assist in
  403.         establishing a schedule to identify locations of
  404.         products in the project; coordinate with drawings.
  405.         Delete entire Article if not required.
  406.  
  407. 3.4 SCHEDULES
  408.  
  409.     A.  Area Designation:  Reception.
  410.         1.  North and West walls:  Acoustical fabric panel
  411.             system, Panel Type 1; horizontal wall panel, radius
  412.             edge, with reveal.
  413.             a.  Panel core material:  Acoustical core.
  414.             b.  Panel fabric:  Type A.
  415.             c.  Reveal:  Laminated wood, black lacquer finish.
  416.         2.  East Wall:  Glazed curtain wall.
  417.         3.  South Wall:
  418.             a.  Desk front:  Acoustical fabric panel system,
  419.                 Panel Type 2; horizontal puff panel, radius edge,
  420.                 with reveal.
  421.                 1)  Panel core material:  Nailable core base, 2
  422.                     layers acoustical core.
  423.                 2)  Panel fabric:  Type B.
  424.                 3)  Reveal:  Stainless steel, Number 7 finish.
  425.             b.  Soffit:  Acoustical fabric panel system, Panel
  426.                 Type 3; horizontal panel, radius edge, with
  427.                 reveal.
  428.                 1)  Panel core material:  Nailable core base for
  429.                     mounting corporate logo.
  430.                 2)  Panel fabric:  Type B.
  431.                 3)  Reveal:  Stainless steel, Number 7 finish.
  432.  
  433.     B.  Area Designation:  Conference.
  434.         1.  North wall:  Acoustical fabric panel system, Panel
  435.             Type 4; full-height wall panel, monolithic edge,
  436.             abutted joints.
  437.             a.  Panel core material:  Acoustical core and
  438.                 tackable core; locations indicated on drawings.
  439.             b.  Panel fabric:  Type C.
  440.         2.  All other walls::  Acoustical fabric panel system,
  441.             Panel Type 5; full-height wall panel, monolithic
  442.             edge, abutted joints.
  443.             a.  Panel core material:  Acoustical core.
  444.             b.  Panel fabric:  Type D.
  445.  
  446.     C.  Area Designation:  A/V Presentation Room.
  447.         1.  All walls:  Noise-reducing acoustical fabric panel
  448.             system, Panel Type 6; full-height wall panel, radius
  449.             edge, abutted joints.
  450.             a.  Panel core material:  Noise-reducing core.
  451.             b.  Panel fabric:  Type E.